Background: Beam-to-box-column connections are considered among the critical regions of steel moment-resisting frames due to the limitations associated with the installation of internal continuity plates, and their seismic performance depends on the reliability of construction details. In this study, the effect of the installation method of horizontal continuity plates on the cyclic behavior of beam-to-box-column connections and their ability to develop the desirable weak-beam–strong-column mechanism was investigated.
Methods: For this purpose, two full-scale beam-to-box-column connection specimens were designed, fabricated, and subjected to cyclic loading in accordance with the AISC 341-22 loading protocol. Both specimens had similar geometry and structural characteristics, with the main difference being the method used to connect the internal continuity plate to the column wall. Electroslag welding (ESW) was used in specimen N01, whereas shielded metal arc welding (SMAW) was employed in specimen N02. After fabrication, the quality of the welds in the connection region was inspected, and the hysteretic behavior, envelope curves, failure mechanisms, and energy dissipation capacities of the specimens were evaluated.
Results: The results showed that, despite weld quality control, premature damage occurred in the connection region of specimen N01. Fracture of the continuity-plate weld at a drift ratio of approximately 1.5% led to damage concentration in the connection and prevented the development of a significant plastic hinge in the beam. This specimen reached only approximately 0.7 times the nominal plastic moment capacity of the beam (0.7Mp), whereas specimen N02, through the development of plastic deformations in the beam, reached approximately 1.3 times the nominal plastic moment capacity (1.3Mp). In addition, the post-yield stiffness ratios of specimens N01 and N02 were approximately −1% and 7.8%, respectively. The cumulative dissipated energy of specimen N02 was approximately 232 kJ, which was about 1.8 times the 128 kJ obtained for specimen N01.
Conclusion: The results demonstrated that merely providing the required strength of the connection components and confirming the initial weld quality cannot guarantee satisfactory seismic performance of box-column connections. The sensitivity of internal construction details can alter the damage-development path and prevent full utilization of the beam capacity. Therefore, developing connection details with improved quality-control capability and higher reliability can play an important role in enhancing the seismic performance of such connections
کلیدواژهها English